Incident Management
In Zebrix Control, an incident refers to the creation or update of an external notification triggered by a change in an equipment’s status.
Incidents allow you to automatically alert your teams through one or multiple communication channels.
Incident management is based on three complementary levels:
- Notification Channel: Defines the communication method (email, Teams, ServiceNow, webhook, etc.)
- Incident Connector: Defines when the channel is triggered (incident opening, closing, or both)
- Incident Configuration: Defines which status levels trigger the incident
These three elements work together following a hierarchical logic:
Configuration → Connector → Channel
Notification Channels
A notification channel is the technical method used to send alerts to an external platform.
Detailed documentation:
Email configuration
Teams configuration
Webhook configuration
Discord configuration
Slack configuration
ServiceNow configuration
Easy Vista Configuration
Incident Connector
The connector links one or multiple channels to a triggering behavior.
To add a connector:
- Go to Configuration → Incidents → Connectors
- Click ➕ Add
- Complete the following fields:
- Name: Provide a descriptive name
- Channel: Select one or more notification channels
- Opening / Closing: Specify whether the connector should be triggered on incident opening, closing, or both
Example: If both opening and closing are enabled for a ServiceNow connector, a ticket will automatically be created when the alarm appears and closed when it is resolved.
Incident Configuration
The incident configuration defines which alert levels trigger a notification.
To create a configuration:
- Go to Configuration → Incidents → Configuration
- Click ➕ Add
- Complete the following fields:
- Name: Provide a descriptive name
- Trigger Level: Select the alert level that initiates the incident
- Trigger Level Scope:
- Only this level: The incident will be triggered only when the alert matches the selected level exactly.
- This level and worse: The incident will be triggered for the selected level and all higher severity levels.
- Example: A configuration set to Warning will trigger incidents for Warning, Critical, and Unreachable alarms.
- Connectors: Select the connector(s) to associate with this configuration